Scope of application
It is suitable for the test of power system CT volt-ampere characteristics, PT volt-ampere characteristics, CT transformation ratio polarity, PT transformation ratio polarity, and transformer secondary load.
Performance characteristics
(1) Combine CT (PT) volt-ampere, CT (PT) transformation ratio polarity, inflection point voltage and current, secondary load, channel, fixed value, 10% (5%) error curve, rated no-load loss, and multiple Functional device
(2) Multi-winding (multi-channel) synchronous test, 6 sets of CT secondary winding transformation ratio tests are completed at one time; transformation ratio and polarity tests are completed at the same time;
(3) Arbitrary setting of characteristic value of volt-ampere test;
(4) Real-time test curve and data display, intelligent misoperation prompt;
(5) The test output voltage is isolated from the input power supply with multiple protections (protection against overload, short circuit, software, etc.).
Technical index
Maximum output capacity | 5kVA |
The output voltage | 0~2500V·2A;0~2000V·2A;0~1000V·5A; 0~500V·10A;0~250V·20A;0~125V·20A; 0~50V·20A;0~15V·20A |
Maximum output current | 1A、2A、3A、4A、5A、10A、15A、20A |
Maximum output current | 1000A·5V |
Secondary load measurement range | 1A:0~10Ω;5A:0~2Ω |
Secondary current channel | 6 way |
measurement accuracy | One measurement voltage: ±(0.5%+0.2V), secondary measurement voltage: ±(0.5%+2 words) primary measurement current: ±(0.5%+0.2A), secondary measurement current: ±(0.5%+ 2 words) |
Protection function settings | Triple overload protection: maximum current setting value protection; total current overload fast electronic protection; total current overload fast switch protection |