Transformer testing vehicle

Transformer testing vehicle


Invention patent certificate number

ZL201110195740.1

 The first domestic on-board integrated 500kV transformer field calibration system

        Through long-term research and accumulation, Suzhou Huadian has formed four types of products in the field of high-voltage measurement equipment: 1. High-stability AC and DC high-voltage power supplies; 2. High-precision digital kilovolt meters; 3. Standard transformers and transformer calibration Inspection of complete sets of equipment; 4. On-site inspection of transformers. It has been widely used in the national electric power research institutes and the measurement centers of the provincial technical supervision bureaus. In accordance with the requirements and specifications of the State Grid Corporation's Electric Energy Metering Center, Suzhou Huadian will provide complete supporting equipment and intelligent package solutions for the comprehensive development of high-voltage metering work in the power system.

     The power transformer field verification vehicle combines the power transformer field verification device with a special vehicle specially designed and equipped with mechanized equipment and auxiliary functions to realize the motorization, intensive and intelligentization of the power transformer field verification. All instruments and equipment for transformer calibration are centrally installed inside the vehicle, with mechanical equipment such as hydraulic lifting platform, roof electric windows, hydraulic loading and unloading machines, and hydraulic support legs to facilitate and flexibly complete the on-site operation of electric transformers. Computers and centralized control software are used to centrally control the calibration equipment to realize automatic operation of transformer calibration. According to the voltage level, it can be divided into three types: 500kV, 220kV and 110kV, 110kV and below. Can meet the corresponding voltage level CT, CVT, PT and GIS built-in transformer error detection and calibration.

Automatic deployment test platform, standard boost integrated device, centralized control operation room on the vehicle

System parameters

Vehicle quality

≤18吨

Vehicle size(mm)

9150*2550*3950

Rated output

350kV

Rated test capacity

253kVA

Rated output frequency

50Hz

Standard accuracy

0.025,0.05level

Test voltage stability

1.0%

Test voltage waveform

Sine wave

220kV/330kV transformer testing vehicle

PT、CTOn-site inspection and verification

Invention patent certificate number

ZL200910115431.1

Top-out type boost/pressure measurement integrated device, large current high-level lead, centralized control operation room on the car

System parameters

Vehicle quality

≤18Ton

Vehicle size(mm)

9150*2550*3950

Rated output

160kV/230kV

Rated test capacity

108kVA/137.5kVA

Rated output frequency

50Hz

Standard accuracy

0.025,0.05level

Test voltage stability

1.0%

Test voltage waveform

Sine wave

 

110kV/220kV transformer testing vehicle

Meet the 110kV~220kV voltage level transformer field verification

Rear pull type boost/pressure measurement integrated device, lightweight design, centralized control operation room on the vehicle.

System parameters

Model

Iveco/Benz

Vehicle quality

≤5Ton

Vehicle size(mm)

6943*1993*2975

Rated output

80kV/160kV

Rated test capacity

52.5kVA/105kVA

Rated output frequency

50Hz

Standard accuracy

0.025,0.05level

Test voltage stability

1.0%

Test voltage waveform

Sine wave

 

Product development
Suzhou Huadian also designs and manufactures transformers on-site calibration according to various voltage levels, and develops various automatic lifting and shrinking mechanical structures to achieve the high efficiency of transformer on-site testing.


  • Core technology and innovation
  • patented technology
  • Field Test

Contact us

No. 255, Shanpu Road, Hedong Industrial Park, Wuzhong Economic Development Zone, Suzhou City, Jiangsu Province

Tel:+86-512-67266386

Fax:+86-512-67167303

szhd@szhddq.com